The GE IS200STTCH2ABA (IS230SNTCH4A) is a high-density Thermocouple Terminal Board designed for Mark VIe turbine control systems. It provides a reliable interface for field thermocouple wiring, enabling accurate temperature data acquisition when paired with PTCC I/O packs. The modular design supports simplex, duplex, or TMR configurations, making it suitable for critical turbine monitoring and control applications.
Multi-Channel Capability: Handles up to 24 thermocouple inputs, supporting extensive turbine temperature monitoring.
Wide Thermocouple Support: Compatible with standard types, including J, K, E, T, S, B, R, and N.
Cold Junction Compensation (CJC): Features integrated thermistors near terminal points to ensure precise ambient temperature correction.
Compact, Maintenance-Friendly Design: DIN-rail or panel mounting with removable Euro-style terminal blocks simplifies installation and service.
Passive Reliability: As a passive terminal board, it achieves high MTBF, relying on removable PTCC packs for signal digitization.
Automatic Identification: Includes an onboard ID chip for seamless recognition by the Mark VIe system, preventing configuration errors.
1. High-Density Signal Termination
Provides a landing point for up to 24 thermocouple inputs, ideal for monitoring multiple turbine temperature zones.
Designed to preserve signal integrity, minimizing electrical noise on millivolt thermocouple lines.
2. Accurate Temperature Compensation
Built-in CJC sensors ensure that ambient temperature at the connection point is accounted for in final readings.
Maintains high precision for low-voltage thermocouples, including Type S and Type R, commonly used in high-temperature applications.
3. Flexible Redundancy Options
Compatible with Simplex or TMR (Triple Modular Redundant) configurations.
Passive design reduces failure risk, while I/O packs handle active signal processing.
4. Diagnostic Support
When used with PTCC packs, the system can detect open circuits, shorted wires, or configuration mismatches.
Supports software-defined alerts for out-of-range or abnormal thermocouple readings.
5. Service-Friendly Engineering
Screw-type Euro-style terminals provide secure, vibration-resistant connections.
Compact footprint allows PTCC I/O packs to mount directly on the board, eliminating external cabling and simplifying cabinet layout.
| Feature | Specification |
|---|---|
| System Compatibility | GE Mark VIe |
| Channels | 24 Thermocouple Inputs |
| Terminal Type | Two 48-point Euro-style terminal blocks |
| CJC Sensors | 2 Integrated Thermistors |
| Mounting Options | DIN-rail or Cabinet Wall Mount |
| Supported Thermocouples | J, K, E, T, S, B, R, N |
| Paired I/O Packs | IS220PTCCH1/H2 PTCC |
| Passive MTBF | Very High, electronics handled by PTCC pack |
High-density turbine temperature monitoring in gas and steam plants
Integration into Mark VIe turbine control cabinets
Safety-critical monitoring using simplex or TMR configurations
Monitoring exhaust, bearing, and casing temperatures for turbine protection
Q: How many thermocouple channels can this board support?
A: Up to 24 channels depending on configuration and paired I/O packs.
Q: Which thermocouple types are compatible?
A: Supports J, K, E, T, S, B, R, and N types.
Q: Is the board compatible with TMR setups?
A: Yes, it supports simplex, dual, and TMR configurations.
Q: How is cold junction compensation handled?
A: Two onboard thermistors provide local CJC near the terminal blocks for precise ambient temperature correction.